Below sea ray lighting in outdoor basketball court, for example introduces general outdoor basketball court lighting scheme selected lamp type and cloth lamp: lighting, outdoor stadium site installation lamp different ways are not the same. Standard according to the course to use a function to determine the illumination of the
the following sea ray lighting in outdoor basketball court, for example introduces general outdoor basketball court lighting scheme selected lamp type and cloth lamp:
outdoor stadium lighting, site installation lamp different ways are not the same. Standard according to the course to use a function to determine the standard of illumination, probably is divided into the following grades:
intensity of illumination 120 - training and entertainment activities 300 lx;
300 - amateur competitions 500 lx;
500 - professional game 800 lx;
general TV broadcast 1000 lx or higher;
large international high-definition television 1400 lx, TV emergency 750 lx.
outdoor basketball court routine luminaires:
( 1) Layout: four corners and concentrated form of lamps and lanterns and light pole, the combination of layout in the corners of the venue.
( 2) Mixed arrangement: layout combined with four arrangement on both sides.
( 3) Right: combination of lamps and lanterns and light pole or building. In the form of a continuous band or clusters of concentrated form arranged on both sides of the venue.
outdoor basketball court lighting solution 1:
the luminaires: stadium on both sides of the stud cloth lamp;
cloth lamp quantity: four groups;
configuration in each group: 8 m tapered steel + 2 400 w metal halide lamp light pole floodlight;
unilateral two lamp spacing: 16 meters;
the pitch: the average illuminance on the ground 420 lux.
this solution is mainly suitable for: general ordinary basketball venues, including training, entertainment, competition, such as: community center, factory basketball court, community, etc.
outdoor basketball court lighting solution 2:
the luminaires: stadium on both sides of the stud cloth lamp;
cloth lamp quantity: four groups;
configuration in each group: 8 m tapered steel + 3 400 w metal halide lamp light pole floodlight;
unilateral two lamp spacing: 16 meters;